0022 | Product Group Code |
ACTUATION TYPE | Push-in || Operating tool |
APPROVALS PER | UL 1059 |
CATALOG NUMBER | 2002-1611/1000-867 |
COLOR | Gray |
CONNECTABLE CONDUCTOR MATERIALS | Copper |
CONNECTION TECHNOLOGY | Push-in CAGE CLAMP |
CONTINUOUS OPERATING TEMPERATURE | -60 +105 C |
Country of Origin | Germany |
DEPTH FROM UPPER EDGE OF DIN RAIL | 57.2 mm / 2.252 inches |
FINE STRANDED CONDUCTOR | 0.25 4 mm / 22 12 AWG |
FINE STRANDED CONDUCTOR WITH FERRULE PUSH IN TERMINATION | 1 2.5 mm / 18 14 AWG |
FINE STRANDED CONDUCTOR WITH INSULATED FERRULE | 0.25 2.5 mm / 22 14 AWG |
FIRE LOAD | 0.211 MJ |
FLAMMABILITY CLASS PER UL94 | V0 |
Features | DEKRA Certification B.V., CCA, 71-120369, EN 60947| CQST/CNEx, CCCEx, 2020312313000180, CNCA-C23-01| DEKRA Certification B.V., CCA, NTR NL 7892, EN 60947| American Bureau of Shipping, ABS, 20-HG1941090-PDA, EN 60947| KIWA Netherlands B.V., IECEx, IECEx KIWA 17.0014U Ex ec IIC Gc, EN 60079| KIWA Netherlands B.V., ATEX, KIWA 17ATEX0030 U, EN 60079| Det Norske Veritas, Germanischer Lloyd, DNV GL, TAE00001V2| Underwriters Laboratories Inc., UL, E45172, UL 1059 |
GTIN | 4050821214298 |
HAZARDOUS AREAS | See Downloads Documentation Additional Information: Technical Section; Technical explanations |
INSULATION MATERIAL | Polyamide (PA66) |
LEGEND RATINGS | (III / 3) ? Overvoltage category III / Pollution degree 3 |
MARKING LEVEL | Center/side marking |
MATERIAL GROUP | I |
MOUNTING TYPE | DIN-35 rail |
Main Category | Rail / Chassis Terminal Blocks |
Manufacturer | WAGO USA |
NOMINAL CROSS SECTION | 2.5 mm |
NOMINAL VOLTAGE III 3 | 250 V |
NOTE CONDUCTOR CROSS SECTION | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination. |
NOTE MATERIAL DATA | Information on material data can be found here |
NOTE RATED CURRENT | Leakage current in case of a blown fuse: LED 2 mA |
OPERATION STATUS INDICATOR | 120 V |
PACKAGING TYPE | Box |
POWER LOSS MAX PL MAX NOTE | When selecting glass cartridge fuses, make sure that the maximum power loss listed below is not exceeded. The power loss is determined according to IEC or EN 60947-7-3/VDE 0611-6 at 23C. The temperature rise of the terminal block must be checked according to their application and mounting. Higher ambient temperatures represent an additional impact on miniature fuses. Therefore, in such applications, the rated current must be reduced if necessary. More details are available from the manufacturers. |
POWER LOSS PL 3 MAX | 2.5 W |
POWER LOSS PL MAX OVERLOAD AND SHORT CIRCUIT PROTECTION GROUP ARRANGEMENT | 1.6 W |
POWER LOSS PL MAX OVERLOAD AND SHORT CIRCUIT PROTECTION INDIVIDUAL ARRANGEMENT | 1.6 W |
POWER LOSS PL MAX SHORT CIRCUIT PROTECTION GROUP ARRANGEMENT | 2.5 W |
PROCESSING TEMPERATURE | -35 +85 C |
Primary UPC | 4050821214298 |
Product Description | WAGO 2002-1611/1000-867 2-conductor fuse terminal block; with pivoting fuse holder; with end plate; for 5 x 20 mm miniature metric fuse; with blown fuse indication by LED; 120 V; for DIN-rail 35 x 15 and 35 x 7.5; 2.5sq.mm; Push-in CAGE CLAMP; 2 50sq.mm; gray 60401202 |
Product Name | TOPJOBS fuse disconnect terminal block; with pivoting fuse holder for 5 x 20 mm fuse; with blown fuse LED indication for 120 V; rail mount; 2-conductor; 6.2 mm wide; gray |
RATED CURRENT | 6.3 A |
RATED CURRENT CSA USE GROUP B | 6.3 A |
RATED CURRENT CSA USE GROUP C | 6.3 A |
RATED CURRENT EX E II | 6.3 A |
RATED CURRENT UL USE GROUP B | 10 A |
RATED CURRENT UL USE GROUP C | 10 A |
RATED CURRENT UL USE GROUP D | 10 A |
RATED IMPULSE VOLTAGE III 3 | 6 kV |
RATED VOLTAGE CSA USE GROUP B | 250 V |
RATED VOLTAGE CSA USE GROUP C | 250 V |
RATED VOLTAGE EN EX E II | 120 V |
RATED VOLTAGE UL USE GROUP B | 120 V |
RATED VOLTAGE UL USE GROUP C | 120 V |
RATED VOLTAGE UL USE GROUP D | 120 V |
RATINGS NOTE | Electrical ratings are given by the fuse and blown fuse indication. |
RATINGS PER | ATEX: KIWA 17 ATEX 0030 U / IECEx: KIWA 17.0014U (Ex ec IIC Gc) |
SOLID CONDUCTOR | 0.25 4 mm / 22 12 AWG |
SOLID CONDUCTOR PUSH IN TERMINATION | 0.75 4 mm / 18 12 AWG |
Short Description | TOPJOBS fuse disconnect terminal block; with pivoting fuse holder for 5 x 20 mm fuse; with blown fuse LED indication for 120 V; rail mount; 2-conductor; 6.2 mm wide; gray |
Sub Category | Fuse terminal block |
WIRING DIRECTION | Front-entry wiring |